Total 4731 registered members
Compact NSX – prekidač nove generacije

Compact NSX 100A–630A | prekidač nove generacije

Stari Compact NS (100A-630A) definitivno odlazi u penziju, pošto je dugo bio prisutan na tržištu kao jedan od najpouzdanijih prekidača. Zameniće ga mlađi brat Compact NSX, moderan prekidač sa daleko više funkcija i mogućnosti, koji dugo neće imati konkurenciju na polju prekidača do 630A sa mogućnostima kao što su mikroprocesorska zaštita, komunikacija, vizuelni displej, daljinski monitoring energije i snage itd. Budući da je konkurencija na polju izuzetno jaka (ABB, Siemens…), Schneider Electric nije gubio vreme i razvio je ovaj prekidač nove generacije. Budući da cena skoro uvek igra presudnu ulogu kod odlučivanja Investitora ili Panel Builder-a koji tip prekidača koji će se naći u razvodnom ormanu – cena Compact NSX prekidača je čak i niža od starog Compact NS. Odnos cena/kvalitet je kod NSX-a značajno veći nego kod starog NS-a.

Nova mogućnost praćenja potrošnje električne energije kod malih potrošača pojedinačno, pruža detaljnu analizu energetske efikasnosti, kao i mogućnost velike uštede i energije i finansijskih sredstava.

Karakteristike prekidača Compact NSX

  • Nazivna struja: 16 do 630 A
  • 6 nivoa prekidnih moći 25 do 150 kA na 415 V (pogledaj detaljnije)
  • Nazivni napon: do 690 V
  • 2 veličine kućišta za ceo opseg 16 do 630 A
  • Verzija sa 3 i 4 pola
  • Fiksna i izvlačiva izvedba
  • Rastavljanje sa pozitivnom indikacijom prekida
  • Širok opseg zaštitnih jedinica: termomagnetna, elektronska, mikroprocesorska zaštita
  • Diferencijalna zaštita pomoću dodatnih Vigi modula
  • Merenje osnovnih električnih parametara: I, U, P, E, THD, f, CosF
  • Širok opseg pomoćnog pribora i dodataka koji se mogu ugrađivati na samom mestu ugradnje
  • Plug and Play sistem ožičenja komunikacije kao i opseg dodatnih opcija (eksterni displej, modul za održavanje…)
  • Usaglašenost sa medjunarodnim standardima: IEC 60947-1 i 2, Nema, IEC 68230 za klasu tropikalizacije 2
  • Usklađenost za najzahtevnijim specifikacijama kompanija za klasifikaciju u brodogradnji:Bureau Veritas, Lloyd’s Register of Shipping, Det Norske Veritas, RINA.

.
Kompaktni dizajn i vrlo jednostavna ugradnja mikroprocesorske jedinice MICROLOGIC.
(zarotiraj da vidiš!)
….

Primena prekidača Compact NSX:

  • Standardne aplikacije sa standardnim strujama kratkog spoja: zgradarstvo, industrijske zgrade i postrojenja, bolnice…
  • Primene koje zahtevaju visoke prekidne moći: procesna industrija, metalurgija
  • Posebno zahtevne aplikacije: brodogradnja
  • Specifične aplikacije: agresivne sredine, 400Hz, 16 2/3 Hz
  • Aplikacije kod kojih je obavezno merenje potrošnje električne energije svakog potrošača

.

Eksterni displej FDM121 | Micrologic | Komunikacija

Eksterni displej FDM121 | Komunikacija

Kroz direktan pristup detaljnim informacijama, kao i umrežavanjem preko otvorenog protokola (Modbus), Compact NSX omogućava operaterima da optimizuju upravljanje svojim električnim instalacijama i sistemima. Compact NSX može da meri I, U, P, E, THD, f, CosF, zatim procesuira određene akcije, kao i da prikazuje važne podatke na više načina (na direktno ugrađenom ekranu, prednjem panelu ćelije razvodnog ormana sa FDM121, ili daljinski preko POWERLOGIC monitoring sistema – Scada sistema). Compact NSX ima specifične module za kontrolu motora koji omogućuju zaštitu od struje kratkog spoja, preopterećenja, faznog disbalansa i gubitka struje. U kombinaciji sa kontaktorom Schneider Electric-a, prekidač Compact NSX ispunjava sve uslove tipa 2 koordinacije (type 2 coordination) snage do 315kW na 415V prema IEC standardu 60947-4-1. Jedinice za okidanje (trip units) u Compact NSX-u su opremljene sa moment-limitiranim šrafovima i MITOP integrisanim uređajem za okidanje, koji dozvoljavaju da budu ugrađene tačno na svoje mesto u prekidaču. Jednom kada se nameste, električno testiranje više nije potrebno. Pre-ožičeni komunikacioni kablovi i “plug-and-play” interfejs omogućavaju jednostavnu i laku integraciju sa komunikacionim mrežama.

Korisnici mogu da prilagođavaju alarm za sve parametre , biraju prioritete koji će biti prikazani na displeju MICROLOGIC-a ili FDM121, kao i podešavaju vreme režima odlaganja akcije. Konstantno aktiviran zapis log-ova od svih događaja na prekidaču (log events) pružaju korisne informacije instalaterima nakon događaja (kratkog spoja, iznenadnog isključenja…).

.
Dodatna oprema za fiksni prekidač Compact NSX
(stani mišem da vidiš!)

Korisni linkovi sa dokumentacijom za Compact NSX:

.

Related articles

Proračun gromobranske zaštite

Proračun gromobranske zaštite

Nova verzija ePlusMenuCAD–a 8.5.4 bi trebalo da se pojavi sredinom decembra ove godine. Dosta toga će biti korigovano i ispravljeno, a najveća novina će definitivno biti kompletan proračun gromonbranske zaštite za koji je zaslužan Dalibor Vranješ, koji je odradio ovo na sjajan način i podelio to sa nama, kao i sa svim korisnicima ePlusMenuCAD-a. CsanyiGroup se ovim putem zahvaljuje Daliboru na kodu koji je podelio sa nama, i koji će nesumnjivo puno koristiti projektantima pri izradi proračuna gromobranske zaštite.

Reč autora: “Ovaj program je urađen da zadovolji projektante gromobranske zaštite za stambene i poslovne objekte gdje se gromobranska zaštita izvodi klasičnim sistemom (hvataljke i spustovi). Primjenom ovog podprograma se ubrzava izrada proračuna i izbor stepena zaštite od gromobranskog pražnjenja. Skraćuje se vrijeme za izradu projekta, jer se izvještaj generiše automatski.

Dalibor Vranješ kontakt i detalji proračuna:

Profil na Google-u:Pogledaj
Detalji proračuna gromobranske zaštite:Pogledaj

.

Edvard Csanyi, CsanyiGroup

.

Related articles

What to use? Vacuum or SF6 circuit breaker?

What CB to use? Vacuum or SF6 circuit breaker?

Until recently oil circuit breakers were used in large numbers for Medium voltage Distribution system in many medium voltage switchgears. There are number of disadvantages of using oil as quenching media in circuit breakers. Flammability and high maintenance cost are two such disadvantages! Manufacturers and Users were forced to search for different medium of quenching. Air blast and Magnetic air circuit breakers were developed but could not sustain in the market due to other disadvantages associated with such circuit breakers. These new types of breakers are bulky and cumbersome. Further research were done and simultaneously two types of breakers were developed with SF6 as quenching media in one type and Vacuum as quenching media in the other. These two new types of breakgasers will ultimately replace the other previous types completely shortly. There are a few disadvantages in this type of breakers also. One major problem is that the user of the breakers are biased in favour of old fashioned oil circuit breakers and many of the users always have a step motherly attitude to the new generations of the breakers. However in due course of time this attitude will disappear and the new  type of breakers will get its acceptance among the users and ultimately they will completely replace the oil circuit breakers. An attempt is made to make a comparison between the SF6 type and vacuum type circuit breakers with a view to find out as to which of the two types is superior to the other. We will now study in detail each type separately before we compare them directly.

Vacuum Circuit Breaker
Evolis Circuit Breaker

Evolis MV Circuit Breaker

In a Vacuum circuit breaker, vacuum interrupters are used for breaking and making load and fault currents. When the contacts in vacuum interrupter separate, the current to be interrupted  initiates a metal vapour arc discharge and flows through the plasma until the next current zero. The arc is then extinguished and the conductive metal vapour condenses on the metal surfaces within a matter of micro seconds. As a result the dielectric strength in the breaker builds up very rapidly.

The properties of a vacuum interrupter depend largely on the material and form of the contacts. Over the period of their development, various types of contact material have been used. At the moment it is accepted that an oxygen free copper chromium alloy is the best material for High voltage circuit breaker. In this alloy , chromium is distributed through copper in the form of fine grains. This material combines good arc extinguishing characteristic with a reduced tendency to contact welding and low chopping current when switching inductive current. The use of this special material is that the current chopping is limited to 4 to 5 Amps.

At current under 10KA, the Vacuum arc burns as a diffuse discharge. At high values of current the arc changes to a constricted form with an anode spot. A  constricted arc that remain on one spot for too long can thermically over stress the contacts to such a degree that the deionization of the contact zone at current zero can no longer be guaranteed . To overcome this problem the arc root must be made to move over the contact surface. In order to achieve this, contacts are so shaped that the current flow through them results in a magnetic field being established which is at right angles to the arc axis. This radial field causes the arc root to rotate rapidly around the contact resulting in a uniform distribution of the heat over its surface. Contacts of this type are called radial magnetic field electrodes and they are used in the majority of circuit breakers for medium voltage application.

A new design has come in Vacuum interrupter, in which switching over the arc from diffusion to constricted state by subjecting the arc to an axial magnetic field. Such a field can be provided by leading the arc current through a coil suitably arranged outside the vacuum chamber. Alternatively the field can be provided by designing the contact to give the required contact path. Such contacts are called axial magnetic field electrodes. This principle has advantages when the short circuit current is in excess of 31.5 KA.

SF6 Gas Circuit Breaker
SF6 circuit breakers

SF6 circuit breakers

In an SF6 circuit-breaker, the current continues to flow after contact separation through the arc whose plasma consists of ionized SF6 gas. For, as long as it is burning, the arc is subjected to a constant flow of gas which extracts heat from it. The arc is extinguished at a current zero, when the heat is extracted by the falling current. The continuing flow of gas finally de-ionises the contact gap and establishes the dielectric strength required to prevent a re-strike.

The direction of the gas flow, i.e., whether it is parallel to or across the axis of the arc, has a decisive influence on the efficiency of the arc interruption process. Research has shown that an axial flow of gas creates a turbulence which causes an intensive and continuous interaction between the gas and the plasma as the current approaches zero. Cross-gas-flow cooling of the arc is generally achieved in practice by making the arc move in the stationary gas. This interruption process can however, lead to arc instability and resulting great fluctuations in the interrupting capability of the circuit breaker.

In order to achieve a flow of gas axially to the arc a pressure differential must be created along the arc. The first generation of the SF6 circuit breakers used the two-pressure principle of the air-blast circuit-breaker. Here a certain quantity of gas was kept stored at a high pressure and released into the arcing chamber. At the moment high pressure gas and the associated compressor was eliminated by the second generation design. Here the pressure differential was created by a piston attached to the moving contacts which compresses the gas in a small cylinder as the contact opens. A disadvantage is that this puffer system requires a relatively powerful operating mechanism.

Neither of the two types of circuit breakers described was able to compete with the oil circuit breakers price wise. A major cost component of the puffer circuit-breaker is the operating mechanism; consequently developments followed which were aimed at reducing or eliminating this additional cost factor. These developments concentrated on employing the arc energy itself to create directly the pressure-differential needed. This research led to the development of the self-pressuring circuit-breaker in which the over – pressure is created by using the arc energy to heat the gas under controlled conditions. During the initial stages of development, an auxiliary piston was included in the interrupting mechanism, in order to ensure the satisfactory breaking of small currents. Subsequent improvements in this technology have eliminated this requirement and in the latest designs the operating mechanism must only provide the energy needed to move the contacts.

Parallel to the development of the self-pressuring design, other work resulted in the rotating – arc SF6 gas circuit breaker. In this design the arc is caused to move through, in effect the stationery gas. The relative movement between the arc and the gas is no longer axial but radial, i.e., it is a cross-flow mechanism. The operating energy required by circuit breakers of this design is also minimal.

Table 1. Characteristics of the SF6 and vacuum current interrupting technologies.

SF6 Circuit BreakersVacuum Circuit Breakers
CriteriaPuffer Circuit BreakerSelf-pressuring circuit-breakerContact material-Chrome-Copper
Operating energy requirementsOperating Energy requirements are high, because the mechanism must supply the energy needed to compress the gas.Operating Energy requirements are low, because the mechanism must move only relatively small masses at moderate speed, over short distances. The mechanism does not have to provide the energy to create the gas flowOperating energy requirements are low, because the mechanism must move only relatively small masses at moderate speed, over very short distances.
Arc EnergyBecause of the high conductivity of the arc in the SF6 gas, the arc energy is low. (arc voltage is between 150 and 200V.)Because of the very low voltage across the metal vapour arc, energy is very low. (Arc voltage is between 50 and 100V.)
Contact ErosionDue to the low energy the contact erosion is small.Due to the very low arc energy, the rapid movement of the arc root over the contact and to the fact that most of the metal vapour re-condenses on the contact, contact erosion is extremely small.
Arc extinguishing mediaThe gaseous medium SF6 possesses excellent dielectric and arc quenching properties. After arc extinction, the dissociated gas molecules recombine almost completely to reform SF6. This means that practically no loss/consumption of the quenching medium occurs. The gas pressure can be very simply and permanently supervised. This function is not needed where the interrupters are sealed for life.No additional extinguishing medium is required. A vacuum at a pressure of 10-7 bar or less is an almost ideal extinguishing medium. The interrupters are ‘sealed for life’ so that supervision of the vacuum is not required.
Switching behavior in relation to current choppingThe pressure build-up and therefore the flow of gas is independent of the value of the current. Large or small currents are cooled with the same intensity. Only small values of high frequency, transient currents, if any, will be interrupted. The de-ionization of the contact gap proceeds very rapidly, due to the electro-negative characteristic of the SF6 gas and the arc products.The pressure build-up and therefore the flow of gas is dependent upon the value of the current to be interrupted. Large currents are cooled intensely, small currents gently. High frequency transient currents will not, in general, be interrupted. The de-ionization of the contact gap proceeds very rapidly due to the electro-negative characteristic of the SF6 gas and the products.No flow of an ‘extinguishing’ medium needed to extinguish the vacuum arc. An extremely rapid de-ionization of the contact gap, ensures the interruption of all currents whether large or small. High frequency transient currents can be interrupted. The value of the chopped current is determined by the type of contact material used. The presence of chrome in the contact alloy with vacuum also.
No. of short-circuit operation10—5010—5030—100
No. full load operation5000—100005000—1000010000—20000
No. of mechanical operation5000—200005000—2000010000—30000

Comparison of the SF6 And Vacuum Technologies

The most important characteristics of the SF6 gas and vacuum-circuit breakers, i.e., of SF6 gas and vacuum as arc-extinguishing media are summarized in Table-1.

In the case of the SF6 circuit-breaker, interrupters which have reached the limiting number of operations can be overhauled and restored to ‘as new’ condition. However, practical experience has shown that under normal service conditions the SF6 interrupter never requires servicing throughout its lifetime. For this reason, some manufacturers no longer provide facilities for the user to overhaul the circuit-breaker, but have adopted a ‘sealed for life’ design as for the vacuum-circuit breaker.

The operating mechanisms of all types of circuit-breakers require servicing, some more frequently than others depending mainly on the amount of energy they have to provide. For the vacuum-circuit breaker the service interval lies between 10,000 and 20,000 operations. For the SF6 designs the value varies between 5,000 and 20,000 whereby, the lower value applies to the puffer circuit-breaker for whose operation, the mechanism must deliver much more energy.

The actual maintenance requirements of the circuit-breaker depend upon its service duty, i.e. on the number of operations over a given period of time and the value of current interrupted. Based on the number of operations given in the previous section, it is obvious that SF6 and vacuum circuit-breakers used in public supply and /or industrial distribution systems will, under normal circumstances, never reach the limits of their summated breaking current value. Therefore, the need for the repair or replacement of an interrupter will be a rare exception and in this sense these circuit-breakers can be considered maintenance-free. Service or maintenance requirements are therefore restricted to routine cleaning of external surfaces and the checking and lubrication of the mechanism, including the trip-linkages and auxiliary switches. In applications which require a very high number of circuit-breaker operations e.g. for arc furnace duty or frequently over the SF6 design, due to its higher summated-breaking current capability. In such cases it is to be recommended that the estimation of circuit-breaker maintenance costs be given some consideration and that these be included in the evaluation along with the initial, capital costs.

Reliability

In practice, an aspect of the utmost importance in the choice of a circuit-breaker is reliability.

The reliability of a piece of equipment is defined by its mean time to failure (MTF), i.e. the average interval of time between failures. Today, the SF6 and vacuum circuit-breakers made use of the same operating mechanisms, so in this regard they can be considered identical.

However, in relation to their interrupters the two circuit breakers exhibit a marked difference. The number of moving parts is higher for the SF6 circuit-breaker than that for the vacuum unit. However, a reliability comparison of the two technologies on the basis of an analysis of the number of components are completely different in regards design, material and function due to the different media. Reliability is dependent upon far too many factors, amongst others, dimensioning, design, base material, manufacturing methods, testing and quality control procedures, that it can be so simply analyzed.

In the meantime, sufficient service experience is available for both types of circuit-breakers to allow a valid practical comparison to be made. A review of the available data on failure rates confirms that there is no discernible difference in reliability between the two circuit-breaker types. More over, the data shows that both technologies exhibit a very high degree of reliability under normal and abnormal conditions.

Switching of fault currents

Today, all circuit-breakers from reputable manufacturers are designed and type-tested in conformance with recognized national or international standards (IEC56). This provides the assurance that these circuit-breakers will reliably interrupt all fault currents up to their maximum rating. Further, both types of circuit-breakers are basically capable of interrupting currents with high DC components; such currents can arise when short circuits occur close to a generator. Corresponding tests have indeed shown that individual circuit-breakers of both types are in fact, capable of interrupting fault currents with missing current zeros i.e. having a DC component greater than 100 per cent. Where such application is envisaged, it is always to be recommended that the manufacturer be contacted and given the information needed for a professional opinion.

As regards the recovery voltage which appears after the interruption of a fault current the vacuum-circuit breaker can, in general, handle voltages with RRV values of up to 5KV. SF6 circuit-breakers are more limited, the values being in the range from 1 to 2 KV. In individual applications, e.g. in installations with current limiting chokes or reactors, etc., With SF6 circuit-breakers it may be advisable or necessary to take steps to reduce that rate of rise of the transient recovery voltage.

Switching small inductive currents

The term, small inductive currents is here defined as those small values of almost pure inductive currents, such as occur with unloaded transformers, motor during the starting phase or running unloaded and reactor coils. When considering the behavior of a circuit-breaker interrupting such currents, it is necessary to distinguish between high frequency and medium frequency transient phenomena.

Medium frequency transients arise from, amongst other causes, the interruption of a current before it reaches its natural zero. All circuit-breakers can, when switching currents of the order of a few hundred amperes and, due to instability in the arc, chop the current immediately prior to a current zero.

This phenomenon is termed real current chopping. When it occurs, the energy stored in the load side inductances oscillates through the system line to earth capacitances (winding and cable capacitances) and causes an increase in the voltage. This amplitude of the resulting over voltage is a function of the value of the current chopped. The smaller the chopped current, the lower the value of the over voltage.

In addition to the type of circuit – breaker, the system parameters at the point of installation are factors which determine the height of the chopping current, in particular the system capacitance parallel to the circuit breaker is of importance. The chopping current of SF6 circuit-breakers is essentially determined by the type of circuit-breaker. The value of chopping current varies from 0.5A to 15A, whereby the behavior of the self – pressuring circuit-breaker is particularly good, its chopping current being less than 3A.This ‘soft’

Switching feature is attributable to the particular characteristics of the interrupting mechanism of the self-pressuring design and to the properties of the SF6 gas itself.

In the early years of the development of the vacuum circuit-breaker the switching of small inductive currents posed a major problem, largely due to the contact material in use at that time. The introduction of the chrome copper contacts brought a reduction of the chopping current to between 2 to 5A.The possibility of impermissible over voltages arising due to current chopping has been reduced to a negligible level.

High frequency transients arise due to pre- or re-striking of the arc across the open contact gap. If, during an opening operation, the rising voltage across the opening contacts, exceed the dielectric strength of the contact gap , a re-strike occurs. The high-frequency transient current arising from such a re-strike can create high frequency current zeros causing the circuit-breaker to, interrupt again. This process can cause a further rise in voltage and further re-strikes. Such an occurrence is termed as multiple restriking.

With circuit- breakers that can interrupt high frequency transient currents, re-striking can give rise to the phenomenon of virtual current chopping. Such an occurrence is possible when a re-strike in the first-phase-to-clear, induces high frequency transients in the other two phases, which are still carrying service frequency currents. The superimposition of this high frequency oscillation on the load current can cause an apparent current zero and an interruption by the circuit-breaker, although the value of load current may be quite high. This phenomenon is called virtual current chopping and can result in a circuit breaker ‘chopping’ very much higher values of current than it would under normal conditions. The results of virtual current chopping are over-voltages of very high values.

This phenomenon is termed real current chopping. When it occurs, the energy Stored in the load side inductances oscillates through the system line to earth capacitances (winding and cable capacitances) and causes an increase in the voltage. This amplitude of the resulting over voltage is a function of the value of the current chopped. The smaller the chopped current, the lower the value of the over voltage.

In addition to the type of circuit – breaker, the system parameters at the point of installation are factors which determine the height of the chopping current, in particular the system capacitance parallel to the circuit breaker is of importance. The chopping current of SF6 circuit-breakers is essentially determined by the type of circuit-breaker. The value of chopping current varies from 0.5A to 15A, whereby the behaviour of the self – pressuring circuit-breaker is particularly good, its chopping current being less than 3A.This ‘soft’   Switching feature is attributable to the particular characteristics of the interrupting mechanism of the self-pressuring design and to the properties of the SF6 gas itself.

In the early years of the development of the vacuum circuit-breaker the switching of small inductive currents posed a major problem, largely due to the contact material in use at that time. The introduction of the chrome copper contacts brought a reduction of the chopping current to between 2 to 5A.The possibility of impermissible over voltages arising due to current chopping has been reduced to a negligible level.

High frequency transients arise due to pre- or re-striking of the arc across the open contact gap. If, during an opening operation, the rising voltage across the opening contacts exceeds the dielectric strength of the contact gap, a re-strike occurs. The high-frequency transient current arising from such a re-strike can create high frequency current zeros causing the circuit-breaker to, interrupt again. This process can cause a further rise in voltage and further re-strikes. Such an occurrence is termed as multiple re-striking.

With circuit- breakers that can interrupt high frequency transient currents, re-striking can give rise to the phenomenon of virtual current chopping. Such an occurrence is possible when a re-strike in the first-phase-to-clear, induces high frequency transients in the other two phases, which are still carrying service frequency currents. The superimposition of this high frequency oscillation on the load current can cause an apparent current zero and an interruption by the circuit-breaker, although the value of load current may be quite high. This phenomenon is called virtual current chopping and can result in a circuit breaker ‘chopping’ very much higher values of current than it would under normal conditions. The results of virtual current chopping are over-voltages of very high values

Table2. Comparison of the SF6 And Vacuum Technologies In Relation To Operational Aspects

CriteriaSF6 BreakerVacuum Circuit Breaker
Summated current cumulative10-50 times rated short circuit current30-100 times rated short circuit current
Breaking current capacity of interrupter5000-10000 times10000-20000 times
Mechanical operating life5000-20000 C-O operations10000-30000 C-O operations
No operation before maintenance5000-20000 C-O operations10000-30000 C-O operations
Time interval between servicing Mechanism5-10 years5-10 years
Outlay for maintenanceLabour cost High, Material cost LowLabour cost Low, Material cost High
ReliabilityHighHigh
Dielectric withstand strength of the contact gapHighVery high

Very extensive testing has shown that, because of its special characteristics the SF6 self-pressuring circuit-breaker possesses considerable advantages in handling high frequency transient phenomena, in comparison with both the puffer type SF6 and the vacuum circuit breakers. The past few years have seen a thorough investigation of the characteristics of vacuum circuit breakers in relation to phenomena such as multiple re-striking and virtual current chopping. These investigations have shown that the vacuum circuit-breaker can indeed cause more intense re-striking and hence more acute over voltages than other types. However, these arise only in quite special switching duties such as the tripping of motors during starting and even then only with a very low statistical probability. The over-voltages which are created in such cases can be reduced to safe levels by the use of metal oxide surge diverters.

Table3. Comparison of the SF6 And Vacuum Switching Technologies In Relation To Switching Applications

CriteriaSF6 Circuit BreakerVacuum Circuit Breaker
Switching of Short circuit current with High DC componentWell suitedWell suited
Switching of Short circuit current with High RRVWell suited under certain conditions (RRV>1-2 kV per Milli secondsVery well suited
Switching of transformersWell suited.Well suited
Switching of reactorsWell suitedWell suited. Steps to be taken when current <600A. to avoid over voltage due to current chopping
Switching of capacitorsWell suited. Re-strike freeWell suited. Re-strike free
Switching of capacitors back to backSuited. In some cases current limiting reactors required to limit inrush currentSuited. In some cases current limiting reactors required to limit inrush current
Switching of arc furnaceSuitable for limited operationWell suited. Steps to be taken to limit over voltage.

.

Related articles

Energetski transformator

Energetski transformator

Energetski transformatori, kako suvi tako i uljni,  se nalaze u skoro svakoj trafo stanici u objektima industrijske namene, ili “building” sektora. Životni vek prosečnog transformatora je oko 30-ak godina uz redovno održavanje i servisiranje. Problemi i posledice koji mogu da nastanu usled uštede na održavanju transformatora (kao i ostale opreme u trafo stanici) mogu biti fatalne za proizvodnju, kao i poslovanje kompanije. U dole prikazanom stručnom tekstu (Andres Tabernero Garcia) je opisan ceo protokol ispitivanja transformatora na licu mesta, prikazani su uređaji sa kojima je vršeno ispitivanje, kao i izveštaji koji su generisani sa njih.

.

Related articles

Integrated Systems for Intelligent Buildings

Integrated Systems for Intelligent Buildings

Intelligent buildings successfully merge building management and IT systems to optimize system performance and simplify facility operations. Integration greatly reduces the expense and frustration associated with installing and operating multiple autonomous building systems.

.

Related articles

Theory and examples of short circuit calculation

Theory and examples of short circuit calculation

An electrical transformer substation consist of a whole set of devices (conductors, measuring and control aparatus and electric machines) dedicated to transforming the voltage supplied by the medium voltage distribution grid (e.g. 12kV or 20kV), into voltage suitable for supplying low voltagelines wit power (400V-690V).

.

Related articles

Proračun pada napona

Proračun pada napona

Voltage drop is the reduction in voltage in an electrical circuit between the source and load. In electrical wiring national and local electrical codes may set guidelines for maximum voltage drop allowed in a circuit, to ensure reasonable efficiency of distribution and proper operation of electrical equipment (the maximum permitted voltage drop varies from one country to another)[1].

Voltage drop may be neglected when the impedance of the interconnecting conductors is small relative to the other components of the circuit.

.

Related articles

Book with graphical explanations of short circuit and its calculations (purpose, standards, types, calculations…)

.

Related articles

Unburied cables:

Cross sections

.

Related articles

1,823 views

What is cascading?

Cascading is the use of the current limiting capacity of circuit breakers at a given point to permit installation of lower-rated and therefore lower-cost circuit breakers downstream. The upstream circuit breakers acts as a barrier against short-circuit currents. In this way, downstream circuit breakers with lower breaking capacities than the prospective short-circuit (at their point of installation) operate under their normal breaking conditions. Since the current is limited throughout the circuit controlled by the limiting circuit breaker, ascading applies to all switchgear downstream. It is not restricted to two consecutive devices.

General use of cascadingcom

With cascading, the devices can be installed in different switchboards. Thus, in general, cascading refers to any combination of circuit breakers where a circuit breaker with a breaking capacity less than the prospective Isc at its point of installation can be used. Of course, the breaking capacity of the upstream circuit breaker must be greater than or equal to the prospective short-circuit current at its point of installation.
The combination of two circuit breakers in cascading configuration is covered by the following standards:

  • IEC 60947-2 (construction)
  • NF C 15-100, § 434.3.1 (installation)
Coordination between circuit breakers

The use of a protective device possessing a breaking capacity less than the prospective short-circuit current at its installation point is permitted as long as another device is installed upstream with at least the necessary breaking capacity. In this case, the characteristics of the two devices must be coordinated in such a way that the energy let through by the upstream device is not more than that which can be withstood by the downstream device and the cables protected by these devices without damage.
Cascading can only be checked by laboratory tests and the possible combinations can be specified only by the circuit breaker manufacturer.

Cascading and protection discrimination

In cascading configurations, due to the Roto-active breaking technique, discrimination is maintained and in some cases, even enhanced.

.

Related articles